blown and needs to be replaced before it can be used again. When overcurrent is triggered, the fault
signal is sent to the VFD through the S1 terminal, and the VFD stops and shuts down the fan through
RO3.
B.4.4.2 Instruction for using GD300-01A with MCP120
M
Control circuit
GND
RLY
24V
CTC
CTB
CTA/Y1
R
S
T
U
V
W
COM
RO3B
24V
Ia
Fan control protector
Ib
Ic
RO3C
GD300-01A
Figure B-71 Wiring for GD300-01A
After completing the wiring according to Figure B-71, set the following parameters in the VFD.
1. P21.01= 1000.
2. Set P21.00 to the corresponding fan rated current. For example, set 2A to be 2.00.
3. P06.02= 29, cooling fan control of main motor. Start/stop of the fan is controlled by NC contact of
the VFD relay RO3.
The fan current detection signals of MCP120-1000 are connected to three signal terminals (Ia, Ib and
Ic) on GD300-01A control board, and start/stop of the fan is controlled by NC contact of the VFD relay
RO3. The fan current signal can be read through the VFD keypad. You can view the fan overcurrent
protection function setting in the P6 group and P21 group settings.
B.5 Filter
Filter model selections for GD300-01A are shown below.
VFD model
Input filter
Output filter
GD300-01A-7R5G-4
FLT-P04032L-B
FLT-L04032L-B
GD300-01A-7R5G-4-CT
GD300-01A-011G-4
GD300-01A-011G-4-CT
GD300-01A-015G-4
FLT-P04045L-B
FLT-L04045L-B