Goodrive300-01A series VFD for air compressor
Function code description
-58-
Function
code
Name
Description
Default Modify
1: Enable input phase loss software protection
Note:
LED ones place detects input phase
loss by phase sequence detection circuit.
LED tens:
0: Disable output phase loss protection
1: Enable output phase loss protection
LED hundreds:
0: Disable input phase loss hardware
protection
1: Enable input phase loss hardware
protection
Note:
LED hundreds place detects input
phase loss by hardware detection circuit.
LED thousands:
0: Disable phase sequence protection
1: Enable phase sequence protection
P11.01
Frequency drop at
transient power dip
0: Disable
1: Enable
0
○
P11.02
Frequency drop rate at
transient power dip
0.00Hz
–P00.03/s (max. frequency)
10.00Hz/
s
○
P11.03
Overvoltage stall
protection
0: Disable
1: Enable
1
○
P11.04
Overvoltage stall
protection voltage
120
–150% (standard bus voltage) (380V)
140%
○
P11.05 Current limit selection
0x00
–0x11
Ones: Current-limit action selection
0: Current-limit action is invalid
1: Current-limit action is always valid
Tens: Hardware current-limit overload alarm
selection
0: Hardware current-limit overload alarm is
valid
1: Hardware current-limit overload alarm is
invalid
01
◎
P11.06
Automatic current-limit
level
50.0
–200.0%
160.0%
◎
P11.07
Frequency drop rate at
current limit
0.00
–50.00Hz/s
10.00Hz/
s
◎