User Manual
248 of 562
V 1.0
2021-08-25
XDPP1100 technical reference manual
Digital power controller
Fault handler
By default GPIO0[2] is assigned to FAULT1 and it outputs Loop 0 faults as selected through PMBus page 0
FW_CONFIG_FAULTS[71:8]. Correspondingly, the GPIO1[2] is assigned to FAULT2 and it outputs Loop 1 faults as
selected through PMBus Page 1 FW_CONFIG_FAULTS[71:8].
9.7
Fault registers
The relevant fault registers and their descriptions are provided in
Table 66
Fault register description
Peripheral Field name
Access Address
Bits
Description
vsen
vsp_osp_thresh
RW
7000_080Ch
(VSEN)
7000_0C0Ch
(VRSEN)
7000_100Ch
(BV(R)SEN)
[11:0]
Open sense protection fault
threshold.
LSB = 1.25 mV, range = 0.0 to
5.11875 V
fault
fault_vout_ov_fault_cnt RW
7000_3C00h
(Loop 0)
7000_4000h
(Loop 1)
[1:0]
Output overvoltage fault count.
Defines the number of 50 MHz
samples the output voltage must
exceed the fault threshold by in
order to assert a fault.
0: 1 sample
1: 2 samples
2: 4 samples
3: 8 samples
fault
fault_vout_ov_warn_cnt RW
7000_3C00h
(Loop 0)
7000_4000h
(Loop 1)
[3:2]
Output overvoltage warning count.
Defines the number of 50 MHz
samples the output voltage must
exceed the warn threshold by in
order to assert a warning.
0: 1 sample
1: 2 samples
2: 4 samples
3: 8 samples
fault
fault_vout_uv_fault_cnt RW
7000_3C00h
(Loop 0)
7000_4000h
(Loop 1)
[5:4]
Output undervoltage fault count.
Defines the number of 50 MHz
samples the output voltage must
exceed the fault threshold by in
order to assert a fault.
0: 1 sample
1: 2 samples
2: 4 samples
3: 8 samples
fault
fault_vout_uv_warn_cnt RW
7000_3C00h
(Loop 0)
7000_4000h
(Loop 1)
[7:6]
Output undervoltage warning
count. Defines the number of
50 MHz samples the output voltage
must exceed the warn threshold by
in order to assert a warning.
0: 1 sample
1: 2 samples