XDPP1100 technical reference manual
Digital power controller
Telemetry
Command name
Access Length Address Bits
Description
MFR_TRANSFORMER_SCA
LE
RW
Word
CEh
[15:0]
Defines the transformer turns ratio,
N
turn_sec
/ N
turn_prim
. The format is
LINEAR11 with recommended
exponents -10, -11, -12
if (N
turn_sec
/ N
turn_prim
is greater than 0.5)
MFR_ TRANSFORMER _SCALE[15:11] =
-10d = 16h
MFR_ TRANSFORMER _SCALE[10:0] =
INT(2^10 * N
turn_sec
/ N
turn_prim
)
else if (N
turn_sec
/ N
turn_prim
is greater than
0.25 )
MFR_ TRANSFORMER _SCALE[15:11] =
-11d = 15h
MFR_ TRANSFORMER _SCALE[10:0] =
INT(2^11 * N
turn_sec
/ N
turn_prim
)
else
MFR_ TRANSFORMER _SCALE[15:11] =
-12d = 14h
MFR_ TRANSFORMER _SCALE[10:0] =
INT(2^12 * N
turn_sec
/ N
turn_prim
)
Note:
When
tlm1_vin_src_sel
= 2
(Loop 0 V
OUT
), set PAGE 1
MFR_TRANSFORMER_SCALE = B3FFh
(0.999) for correct scaling of V
IN
telemetry.
FW_CONFIG_TELEMETRY
RW
Block
21
bytes
C6h
[103:10
0]
READ_DUTY_EXP
: Defines the
LINEAR11 exponent for READ_DUTY
[99:96]
READ_IIN_EXP
: Defines the LINEAR11
exponent for READ_IIN
[95:92]
READ_IOUT_EXP
: Defines the
LINEAR11 exponent for READ_IOUT
[91:88]
READ_VIN_EXP
: Defines the LINEAR11
exponent for READ_VIN
[2:0]
READ_POWER_EXP
: Defines the
LINEAR11 exponent for READ_POUT
and READ_PIN
MFR_SELECT_TEMPERATU
RE_SENSOR
RW
Byte
DCh
[2:0]
Read_Temperature_1_Read_Temper
ature_2_source_select
: Defines the
temp. sense input source selection for
READ_TEMPERATURE_1 and
READ_TEMPERATURE_2 commands.
0: READ_TEMPERATURE_1 = ATSEN,
READ_TEMPERATURE_2 = BTSEN
1: READ_TEMPERATURE_1 = ATSEN,
READ_TEMPERATURE_2 = ITSEN
2: READ_TEMPERATURE_1 = BTSEN,
READ_TEMPERATURE_2 = ATSEN
3: READ_TEMPERATURE_1 = BTSEN,