Abbrevia-
tion
Reference
Description
HFT = n means that n + 1 faults may lead to a loss of the safety function.
MTTF
D
EN ISO 13849-1
Mean time to failure – dangerous
Unit: years
PFH
EN IEC 61508
Probability of dangerous failures per hour
Take this value into account if the safety device is operated in high demand mode or in contin-
uous operating mode, where the frequency of demands for operation made on a safety-related
system occurs more than once per year.
PL
EN ISO 13849-1
Performance level
A discrete level used to specify the capability of safety-related parts of a system to perform
safety-oriented functions under foreseeable conditions. Levels: a–e.
SFF
EN IEC 61508
Safe Failure Fraction [%]
Proportion of safe failures and detected dangerous failures of a safety function or a subsystem
as a percentage of all possible failures.
SIL
EN IEC 61508
EN IEC 62061
Safety Integrity Level
STO
EN IEC 61800-5-2 Safe Torque Off
8.6 Installation
Only Danfoss cables can be used for the installation of the servo system, however cables from other suppliers can be used for the
user connection to the STO terminal
STO DAM (Pins 1 and 2)
on the Decentral Access Module (DAM 510).
N O T I C E
If the application does not require the Safe Torque Off (STO) functionality, build a bridge by conn24 V from the con-
nector
STO 1 IN: +24 V
to
STO 1 IN: +STO
, and from
STO 1 IN: –24 V
to
STO 1 IN: –STO
.
Safety relays that have a plus and minus switching output signal can be directly connected to the servo system to activate STO.
The example in
shows the basic connection to be made for the STO function. A suitable safety device to switch it off
is not supplied by Danfoss. The STO is activated by opening STO+ and STO–.
Table 35: Activation of STO Function
STO+
STO–
STO function
24 V
GND
STO deactivated
Open
GND
STO activated
24 V
Open
STO activated
Open
Open
STO activated
N O T I C E
Do not exceed 30 V at the STO inputs.
STO is activated if the plus input is between –3 V and +3 V.
STO is deactivated if the plus input is b21.6 V and +26.4 V.
AQ262449648484en-000101 / 175R1135 | 149
Danfoss A/S © 2020.08
Functional Safety Concept
VLT® Servo Drive System ISD 510/DSD 510