6.3.3.6
Mounting air gap insulation section
Air gap insulation sections are used for electrical separation, e.g., for electrical segmentation or block separation. These are used on
all or single poles depending on the required function.
The air gap insulation section can be installed with or without a line feed. The installation of the air gap insulation section with line
feed is described in the following. The end cap is mounted to the air gap insulation section without line feed (see Section 6.3.3.8).
NOTE!
Air gap insulation sections must not be installed in curves or bends!
Required tools:
Tape measure
Scribe
Cutting tool (e.g., cordless angle grinder)
File
Crimping tool
Torque wrench (2 Nm) Bit 3 mm
Work steps:
→
Mount the conductor rail pole (Pos. 1), in which the air gap insulation section is to be installed, in the hanger clamps (see Fig.
93).
Fig. 93: Mount the conductor rail pole in the hanger clamps
1