7.2.2
Initial commissioning of the conductor rail system
1.
Each time before the machine/system is started, measure the insulation resistance of the conductor rail system according to
locally applicable technical standards, directives and legal regulations.
2.
Carry out locally required electrical tests.
3.
Perform a complete run along the conductor rail (walking pace).
Remark:
Insulation resistance test according to EN 60204-
1: 2006 ≥ 1 MΩ at a m
easuring voltage of 500 VDC. Exception for
conductor bars, conductor rails and slip rings ≥ 50 kΩ (EN 60204
-1/18.3: 2006)
4.
Visual inspection of the product/system:
→
Current collector undamaged and without signs of heavy wear.
→
Conductor rail components undamaged and in the proper location. No displacements or distortions. Check hanger clamps,
end caps and fixed points in particular!
→
Check that there are no visible signs of heavy wear (chips, plastic parts, etc.). Signs of heavy wear indicate that installation
clearances and their tolerances are not complied with. This can sometimes also be the case for individual sections of the route.
NOTE!
The current collectors must not become caught, stick or scrape!
→
Where necessary, repair any faults and perform setting tasks.