7.2
Testing and initial commissioning
7.2.1
Inspection list
WARNING!
Risk of death due to electrical shock!
Check
Checked
Installation height as per specifications (see Section 3)
All installed components are clean, dry and undamaged.
Installation clearances of the current collectors are as specified
Have the contact surfaces of the sliding contacts been cleaned before commissioning and
soiling, oxidation, pitting corrosion and other impurities removed by means of a brass brush
or abrasive paper (320 grit)?
Are the connecting cables installed without directional and tensile forces? The connecting
cables must not pull on, press against or cause the current collectors to twist.
Are the hanger clamp distances as specified? (see Section 6.3.3.1)
Have the end caps been fitted correctly and to the first and end section?
Are the end cap bars and fixed points properly installed as specified?
Are the insulation profiles properly engaged in all hanger clamps?
Are the rail joints at the connection points and the end caps deburred and correctly aligned?
Are all electrical protection devices installed, tested and functioning? Are covers and barri-
ers in place?
Is the line feed properly connected?
Are all metallic components (such as substructures/support structure) grounded as specified?
Are all screws tightened to the specified tightening torque?
Is the operating area tidy (no parts or tools)?
Has the operating personnel been trained?
All poles of the conductor rail system have been run through with a loose current collector.
The current collector may not stick and must slide in the rail without hindrance
Warning symbol “Electrical Shock” and type plate are installed by the manufacturer at a suit-
able location.
……………………………….
……………………………….
Date
Signature