6.3.3.5.3
Mounting the expansion module without a setting aid
If no setting aids (Order No.: 08-S902-0002P) are available, the individual expansion gaps in the expansion unit or in the expansion
module per conductor rail pole must be set according to the mounting temperature following the mounting and can be read from the
following diagram (see Fig. 91). Fig. 91 was created on the basis of a full temperature range of 40 K and ensures easy setting.
Fig. 91: Example for reading the setting dimension
For example:
This example assumes a hall with a temperature range of 0 to 40°C:
1.)
Measure the mounting temperature (e.g., 22.5°C) and draw a vertical line up to the ascending line.
2.)
Draw a horizontal line from the intersection on the incline line.
3.)
Read and set the expansion gap setting dimension.
The expansion gap does not need to be set symmetrically, e.g., the setting dimension read does not necessarily need to be divided
by two. It is also conceivable to set one area of the expansion gap to “0” while the other area of the expansion gap is set with the
complete setting dimension (in the example: 10 mm).