Fig. 117: Correct position of the clamping unit
Fig. 118: Incorrect position of the clamping unit
For end line feeds, the power can be supplied at the end of the route. An end line feed consists of an end cap with a line feed
clamping unit. The connection is made using a crimping cable lug with a conductor cross-section of 1.5 mm
2
to 6 mm
2
. For phases,
doubly insulated connecting cables must be provided for voltages > 48 V. Basically, use connecting cables only with copper con-
ductors.
→
Only for end line feeds:
Trim the feed cable and strip the insulation to the desired length.
Crimp the crimping cable lug of the end line feed onto the end of the cable. Do
not
remove the crimping cable lug from
the connector for this.
Fig. 119: Mounting the end cap
→
Tighten the cylinder screw to 2 Nm (see Fig. 119).
→
Provide a structural strain relief for the end line feed cable.
→
For a line feed with preassembled cable part, push the clamping unit onto the end of the rail. Possibly loosen the clamping screw
somewhat and push the end cap onto the clamping part and the conductor rail.
After installing the end cap, check the connection for solidity by gently pulling.
If the conductor rail can be pulled out, the line feed clamp is most likely mounted incorrectly (see Fig.
118).
1.
2.
1.
2.
Tighten the end cap with a 3-mm
hexagonal screwdriver to
2 Nm
.
1 = Push end cap on
2 = Pull on the clamping unit