DANGER!
Risk of injury due to falling conductor rails!
The mountings of the conductor rail can fail and the conductor rail can fall down. Components can
be damaged if the following or similar materials are stored in the vicinity of the conductor rail:
Solvents that contain aromatic compounds and evaporate
Coating products and paints
Separating agents or coolants and lubricants
See Sections 3.3 and 2.8.4.
→
Do not store any of the above or similar substances near the conductor rails.
→
In application areas with personnel traffic and at an installation height of 3 m or more, conductor
rails must be secured against falling.
DANGER!
Risk of death due to electrical shock!
Contact with components carrying electrical power can lead to death due to electrical shock or se-
vere injury. Risk of injury due to shock reactions, falling or being thrown across the room due to
electrical shock.
The conductor rail must not be operated under the following circumstances:
→
If the conductor rail is heavily soiled.
→
If the conductor rail becomes wet.
→
If parts under voltage are exposed (insulating profile or the insulation of the connection cable are
damaged).
→
If the hanger clamp or insulation profile fail.
→
If the conductor bar falls down and contacts a conductive material.
Take the following measures:
→
Install the conductor rail out of manual reach.
→
Attach a sign stating “Risk of Death due to Electrical Shock” with the relevant hazard symbol in all
areas with access to parts under voltage.
→
Secure the electrical system according to regulations.
→
The customer must provide grounding for metallic components.
→
The customer must provide protective devices.
→
Install the conductor rail as described in the installation manual.
→
Take environmental conditions into account, perform regular checks, maintain and clean as de-
tailed in the instructions.
→