InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
141
8.1.9
Peripheral Modules Error detection
It is possible to adjust the protection of level 1 (yellow) or level 2 (red) to any configured peripheral
module. If the controller detects that this periphery is missing it issues the corresponding alarm. In
MCB/MGCB applications Warning is issued when WARNING(YEL) option is selected and MPR (Mains
Protect with Reset) is issued when SHUTDOWN(RED) option is selected (this alarm causes MCB to
open and Mains is considered as failed, Fault Reset is required to remove this protection from the
alarm list once inactive).
The corresponding protection can be adjusted.
Alarm level 1 or level 2 is issued when the
controller detects missing periphery (WARNING
(YEL) – level 1, SHUTDOWN (RED) – level 2)