InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
208
Range [units]
0.0 .. 60.0 [s]
Related FW
standard v3.1.0
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as
Force block #1
are started to be
evaluated.
11.2.4.6
Setpoint: ForceBlockDel2
Group
ComProtSetting
Range [units]
0.0 .. 60.0 [s]
Related FW
standard v3.1.0
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as
Force block #2
are started to be
evaluated.
11.2.4.7
Setpoint: ForceBlockDel3
Group
ComProtSetting
Range [units]
0.0 .. 60.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint adjusts the delay after the binary input
deactivated, when the alarms configured as
Force block #3
are started to be
evaluated.
11.2.4.8
Setpoint: ResetActAlarms
Group
ComProtSetting
Range [units]
[-]
Related FW
standard v3.1.0
Description
DISABLED
Pressing of the fault reset button (at any terminal or
external button) resets only
inactive
alarms. Active
alarms remain in the alarmlist unchanged and must be
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...