InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
162
11.2.1.14
Setpoint: PeakAutS/S del
Group
Process control
Range [units]
OFF, 1 .. 3200 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoints adjusts the delay for automatic Peak start/stop function. Set 0
(OFF) to disable Peak automatic start function. See also the setpoints
N
OTE
:
The delay for this function is counted down in any mode if the conditions are
fulfilled (i.e. in OFF when the Mains Import in kW is higher than
).
11.2.1.15
Setpoint: Peak kVA Start
Group
Process control
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
If the object apparent consumption (
the power of 2) exceeds this setpoint for time longer than
the gen-set starts automatically (in SPtM application) or group of gen-sets is
started by InteliMains. Adjusting the
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...