12.1.16.8
Value: Reg16
Group
Info
Units
-
Related FW
standard v3.1.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position plays active role in the power management. Bit 0
represents address 1 etc. This value contains information about controllers
with addresses 1-16.
12.1.16.9
Value: Reg32
Group
Info
Units
-
Related FW
standard v3.1.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position plays active role in the power management. Bit 0
represents address 17 etc. This value contains information about controllers
with addresses 17-32.
12.1.16.10
Value: GL16
Group
Info
Units
-
Related FW
standard v3.1.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position has GCB closed. Bit 0 represents address 1 etc. This
value contains information about controllers with addresses 1-16.
12.1.16.11
Value: GL32
Group
Info
Units
-
Related FW
standard v3.1.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position has GCB closed. Bit 0 represents address 1 etc. This
value contains information about controllers with addresses 17-32.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...