InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
182
Range [units]
1 .. 15000 [A]
Related FW
standard v3.1.0
Description
Auxiliaries Current Transformer ratio
– primary side.
N
OTE
:
For more information on usage of auxiliary measurement of current please
refer to
11.2.2.14
Setpoint: AuxCurrCTsec
Group
Basic settings
Range [units]
/1A, /5A [A]
Related FW
standard v3.1.0
Description
Auxiliaries Current Transformer ratio
– secondary side.
N
OTE
:
Restricted to selection of /5A or /1A.
N
OTE
:
For more information on usage of auxiliary measurement of current please
refer to
11.2.2.15
Setpoint: FixVoltProtSelect
Group
Basic settings
Range [units]
PHASE-NEUTRAL, PHASE-PHASE [-]
Related FW
standard v3.1.0
Description
PHASE-NEUTRAL
The mains/bus voltage protections are based on
phase-to-neutral voltages.
PHASE-PHASE
The mains/bus voltage protections are based on
phase-to-phase voltages.