InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
327
12.1.12.4
Value: AIN CU-2
Group
Analog CU
Units
configurable
Related FW
standard v3.1.0
Description
This is the value of the analog input 2 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for water temperature measurement.
12.1.12.5
Value: AIN CU-3
Group
Analog CU
Units
configurable
Related FW
standard v3.1.0
Description
This is the value of the analog input 3 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for fuel level measurement.
12.1.12.6
Value: AIN CU-4
Group
Analog CU
Units
configurable
Related FW
standard v3.1.0
Description
This is the value of the analog input 4 of the controller. Analog inputs are fully
configurable so the name and units depend on configuration. In the default
configuration the input is used for fuel level measurement.
12.1.13 Group: Bin inputs CU
12.1.13.1
Value: BIN
Group
Bin inputs CU
Units
-
Related FW
standard v3.1.0
Description
This is a bit array containing status of physical binary inputs of the controller.
Bit0 represents BI1, bit1 represents BI2 etc..
N
OTE
:
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...