InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
155
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among all controllers
connected by CAN2 bus.
11.2.1.4
Setpoint: #SysPFCtrl PtM
Group
Process Control
Range [units]
BASEPF, VSHARING [-]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the power factor control type in parallel-to-
mains operation.
BASEPF
The gen-sets are controlled by their power factor control
loops (i.e. as in SPtM) to provide constant power factor
adjusted by the setpoint
. The InteliMains
does not play active role regarding power factor control in
parallel-to-mains operation.
VSHARING
The gen-sets are controlled by the InteliMains through the
VAr sharing line (CAN2 bus). The InteliMains power factor
control mode is selected by the setpoint
N
OTE
:
This type of power factor control is used for import/export
mode only.
N
OTE
:
If the power factor control mode is switched to VSHARING the
must be switched to LDSHARING and the equivalent
must be used.
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...