InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
406
14.2.1.42
Binary output: StartButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
Start
button is pressed on the controller front panel or
Start
button is pressed on any of external local/remote terminals or
start
command is received via communication line or
the input
14.2.1.43
Binary output: MCBButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
MCB
button is pressed on the controller front panel or
MCB
button is pressed on any of external local/remote terminals or
MCB close/open
command is received via communication line or
the input
MCBButton
is activated.
14.2.1.44
Binary output: MGCBButnEcho
Related FW
standard v3.1.0
Description
This output provides 1s pulse when:
MGCB
button is pressed on the controller front panel or
MGCB
button is pressed on any of external local/remote terminals or
MGCB close/open
command is received via communication line or
the input
MGCBButton
is activated.
14.2.1.45
Binary output: MODES: Off mode
Related FW
standard v3.1.0
Description
The output is closed while the controller is currently in OFF mode (either
switched by the mode selector on the front panel or by the input
).
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...