InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
180
required:
Both setpoints (
) must be adjusted to
the same values according to the value of actual Bus nominal voltage. E.g.
Bus nominal is 400 V but Mains nominal is 415 V.
In this case both setpoints need to be adjusted to 400 V and setpoints of
corresponding protections for Mains need to be set assymetrically.
For 415 V on Mains it is typical to open MCB when voltage reaches 440 V or
390 V. Since the setpoint is adjusted to 400 V corresponding protection
setpoints need to be adjusted to
the desired values are reached).
11.2.2.9
Setpoint: Nomin current
Group
Basic Settings
Range [units]
1 .. 10000 [A]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used for adjusting the maximal allowed current at the mains
feeder.
The nominal current is used as the basis (100%) for mains thermal-
overcurrent protection (
), and for short current protection
N
OTE
:
obtain correct mains current readings.
C
AUTION
!
The maximum measurable input current to the controller current terminals is
11A.
W
ARNING
!
Do not discconnect the CT terminals from the controller while there is
nonzero current in the CT primary circuit!
11.2.2.10
Setpoint: NominMainsImp
Group
Basic Settings
Range [units]
1 .. 32000 [kW]
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...