The "cos-phi" factor is widely used instead of power factor for pure harmonic
waveforms, because a simplified method can be used for calculation of it's
value. However, if this simplified method is used for significantly distorted
waveforms, it may provide inaccurate results. This fact causes the controller
"power factor" value may be different from a value measured by another true-
rms measurement device if the waveform contains significant portion of
higher harmonic frequencies.
12.1.1.14
Value: Load Ld char
Group
Mains values
Units
-
Related FW
standard v3.1.0
Description
Character of the Mains load. "L" means inductive load, "C" is capacitive and
"R" is resistive load (power factor = 1).
12.1.1.15
Value: MPf L1
Group
Mains values
Units
-
Related FW
standard v3.1.0
Description
Mains power factor in phase L1.
12.1.1.16
Value: M Ld char L1
Group
Mains values
Units
-
Related FW
standard v3.1.0
Description
Character of the Mains load in the L1 phase. "L" means inductive load, "C" is
capacitive and "R" is resistive load (power factor = 1).
12.1.1.17
Value: MPf L2
Group
Mains values
Units
-
Related FW
standard v3.1.0
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...