11.2.13.13
Setpoint: Ld shedDelay3
Group
Load shedding
Range [units]
0.0 .. 600.0 [s]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust time period for the load shedding stage 3, that
the
must be above the
load shedding output.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.14
Setpoint: Ld reconLevel1
Group
Load shedding
Range [units]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the relative load level for load shedding stage
1 (in % of
is selected) for load reconnection. When
drops below this level for more than
the next load can be reconnected back.
The appropriate load shedding output is either opened automatically when
the condition above is fulfiled (
activation of the input
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.15
Setpoint: Ld reconLevel2
Group
Load shedding
Range [units]
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...