InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
281
Description
This setpoint is used to adjust time period for the load shedding stage 3, that
the
reconnection of next load group.
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.13.23
Setpoint: AutoLd recon
Group
Engine Protect
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint selects whether the reconnection of the load occurs
automatically when the
stays below the
a period of the
or the reconnection must be initiated
manually by the input
N
OTE
:
Learn more about load shedding in the separate chapter
Load shedding
.
11.2.14 Group: Timer settings
11.2.14.1
Setpoint: Timer channel 1
Group
Timer settings
Range [units]
[-]
Related FW
standard v3.1.0
Description
This setpoint adjusts the mode of the
Timer channel #1
. Output from this
channel is available in the combined output
N
OTE
:
See the chapter
Timers
for more details about timers.
11.2.14.2
Setpoint: Timer channel 2
Group
Timer settings
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...