InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
357
13.2.1.31
Binary input: MGCB disable
Related FW
standard v3.1.0
Description
The input is used to disable issuing the MGCB closing command.
If the input is active during synchronizing, the controller will keep the
controller will keep the genset group synchronized without issuing the
MGCB closing command until the input is deactivated or
If the input is active and the MGCB button is pressed in MAN mode
to close the MGCB to dead bus, the MGCB will not be closed until
the input is deactivated and the MGCB button pressed again.
If the input is active and the MGCB is to be closed to dead bus
automatically, the MGCB will not be closed until the input is
deactivated.
13.2.1.32
Binary input: ManualLdRecon
Related FW
standard v3.1.0
Description
This input is used for manual reconnection of the last disconnected part of
the load, if the load has dropped below the setpoint
This input works only if automatic reconnection is disabled, i.e. the setpoint
13.2.1.33
Binary input: FaultResButton
Related FW
standard v3.1.0
Description
This input is used for an external FAULT RESET button mounted on the
switchboard. The function of the input is identical as function of the fault reset
button on the controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
13.2.1.34
Binary input: HornResButton
Related FW
standard v3.1.0
Description
This input is used for an external HORN RESET button mounted on the
switchboard. The function of the input is identical as function of the horn reset
button on the controller front panel.
The input is enabled only if the setpoint
EXTBUTTONS or BOTH.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...