transferred to gen-sets. After pressing MCB button
MCB is opened and MGCB stays closed, gen-sets are
running in Island operation.
Test on load - MGCB is closed, gen-sets synchronized
to the bus, load transferred to gen-sets and MCB
opened. Return of the load to the Mains is adjusted via
setpoint
11.2.2.18
Setpoint: ContrInitMode
Group
Basic settings
Range [units]
PREVIOUS, OFF, MAN, AUT, [-]
Related FW
standard v3.2.0
Description
This setpoint adjusts which mode will be activated when the controllers is
powered on.
11.2.2.19
Setpoint: Local buttons
Group
Basic settings
Range [units] PANEL, EXTBUTTONS, BOTH [-]
Related FW
standard v3.1.0
Description
The setpoint selects which set of control buttons is currently active. Its function
depends on which type of controller is used. Please refer to the section which
suits your controller/display version.
First section deals with the case of IGS-NT with built-in monochrome
display.
Second section deals with the case of IGS-NT-BB with IV5 display.
Third section deals with the case of IGS-NT-BB with IV8.
N
OTE
:
If you have IGS-NT (built-in display) and you use additional IV display all the
sections may be relevant (depending on the type of additional displays).
IGS-NT (built-in monochrome display)
PANEL
The built-in buttons on the controller front panel (IG-NT) or
terminal #1 (IS-NT) are enabled, the binary inputs for
external buttons are disabled.
EXTBUTTONS
The built-in buttons are disabled and the binary inputs for
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...