InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
103
DATA-CDMA:
This option sends a complete archive to the recipient's PC via CDMA modem. A CDMA
modem must be connected either to one of controller COM ports or to one of I-LB modules connected
to the controller via CAN2 bus. The local CDMA network must allow point-to-point data transfers. The
channel address must contain complete telephone number of the recipient's PC where InteliMonitor is
running in Active call receiving mode.
SMS-GSM:
This option sends a short text message (SMS) containing the actual Alarmlist contents to
the recipient's mobile phone via the GSM modem. The channel address must contain complete
telephone number of the recipient's mobile phone.
SMS-CDMA:
This option sends a short text message (SMS) containing the actual Alarmlist contents
to the recipient's mobile phone via the CDMA modem. The channel address must contain complete
telephone number of the recipient's mobile phone.
IB-E-MAIL:
This option sends an e-mail containing the actual Alarmlist contents and latest 20 history
records (only date, time, reason) to the recipient's mailbox via the IB-COM module or IG-IB module.
The channel address must contain valid e-mail address of the recipient.
N
OTE
:
The SMTP settings (SMTP authent,SMTP user name, SMTP password, SMTP address, Contr
mailbox) must be properly adjusted for sending e-mails.
7.7.2
Example of setting
There is an example of setting of Remote Alarm Messaging. In this case active calls we be triggered
on Mains protect and Mains protect with Reset alarms. Message is sent via email to
[email protected] (Channel 1
– available for NTC controller or with any controller with
connected IB-NT or I-LB+), archive is sent via ISDN modem to the 111222333444 (Channel
2) and SMS is sent to the 999111333555 (Channel 3).
It is also possible to adjust number of attempts that controller performs in case of not successful Active
Call
–
Comms settings:
ActCallAttempt
. The language of messages can be changed
–
Comms settings:
Acall+SMS lang
(use Translator and Languages tabs in GenConfig to adjust
languages).
Up to five channels can be used.
7.8
Controller Redundancy
Redundant system is a general term for applications where there are two controllers at each gen-set.
One is the main controller, which controls the gen-set in normal conditions, the other is the redundant
controller, which takes over the control when the main controller fails. Both controllers have identical
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...