>LS, ANEXSYSBLD->LS or T BY PWR.
N
OTE
:
If the import value/setpoint is negative, it actually means export. This function
can be used to protect the system from unwanted export. You may set
maximum export value or you can set it possitive to keep some import even
in cases that there are abrupt load changes.
N
OTE
:
See the setpoint
for details about mains import measurement
methods.
11.2.1.19
Setpoint: TempByPwr Treq
Group
Process control
Range [units]
-
32000 .. +32000 [°C]
Related FW
standard v3.1.0
Force value
possible
YES
Description
The setpoint is used for adjusting the requested temperature for the
Temperature-By-Power
control loop.
The
Temperature-By-Power
is active if the setpoint
BY PWR position and the logical analog input
physical analog input where the temperature is measured.
and
N
OTE
:
As the "regulating action" of the
Temperature-By-Power
control loop is
changing of the group power the regulated value (i.e. some temperature)
must depend on the group power. Typical usage of this function is regulation
of the output temperature of the heating water in a group of CHP units.
11.2.1.20
Setpoint: TempByPwr gain
Group
Process control
Range [units]
0.00 .. 100.00 [%]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the gain factor for the
Temperature-By-Power
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...