InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
221
Force value
possible
YES
Description
This setpoint determines the treshold for bus overfrequency protection. This
protection is evaluated with delay given by setpoint
record type.
11.2.7.5
Setpoint: Bus <f
Group
Bus protect
Range [units]
50.0 ..
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint determines the treshold for bus underfrequency protection. This
protection is evaluated with delay given by setpoint
record type.
11.2.7.6
Setpoint: Bus f del
Group
Bus protect
Range [units]
0.00 .. 600.00 [s]
Related FW
standard v3.1.0
Description
This setpoint adjusts delay for under- (
protections.
N
OTE
:
Although the resolution of this setpoint is 0.01s, in fact the adjusted delay is
rounded to the next higher multiple of the period of the bus voltage. The
period is either 0.02s for 50Hz systems or 0.0166s for 60Hz systems. E.g. if
the delay is set to 0.03s at 50Hz system the real delay will be 0.04s.
11.2.7.7
Setpoint: BusMeasError
Group
Bus protect
Range [units]
DISABLED, ENABLED [-]
Related FW
standard v3.1.0
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...