InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
251
MGCB
forward or reverse synchronization of the gen-set group
to the mains
BTB
synchronization between “left” and “right” buses
N
OTE
:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
11.2.10.6
Setpoint: Freq int
Group
Sync/Load Ctrl
Range [units]
0 .. 100 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the relative integration factor (I-factor) of the frequency
control PI loop. The gain factor (P-factor) for the frequency loop is adjusted
by the setpoint
A
PPLICATION
F
REQ GAIN AND
F
REQ INT SETPOINTS ARE ACTIVE DURING
:
MCB
reverse synchronization of the gen-set group back to the
mains
MGCB
forward or reverse synchronization of the gen-set group
to the mains
BTB
synchronization between “left” and “right” buses
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...