7.6.3.3
Efficiency
The Efficiency mode is a combination of Running Hours Equalization and Load Demand Swap priority
optimization modes. Please refer to chapters 7.6.3.1 and 7.6.3.2 for further information about RHE
and LDS priority optimization function.
In the first step, the controller sorts the gen-sets according to their nominal power.
In the second step, the controller sorts the gen-sets with the same nominal power according to
their RHE.
The gen-set(s) their nominal power fits the most are chosen. From those with same nominal
power, the gen-set(s) with lowest RHE are chosen.
EXAMPLE:
MCB
MGCB
CAN
1
Comms settings:
Contr. Addr = 1
Basic settings:
Nomin power =
300 kW
Pwr management:
#PriorAutoSwap =
EFFICIENCY
Priority ctrl = SLAVE
#RunHrsMaxDiff = 9h
RunHoursBase = 0 h
Control group =
COMMON
Comms settings:
Contr. Addr = 2
Basic settings:
Nomin power =
200 kW
Pwr management:
#PriorAutoSwap =
EFFICIENCY
Priority ctrl = SLAVE
#RunHrsMaxDiff = 9h
RunHoursBase = 0
Control group =
COMMON
Values: Statistics
Run hours = 0
Comms settings:
Contr. Addr = 3
Comms settings:
Nomin power =
200 kW
Pwr management:
#PriorAutoSwap =
EFFICIENCY
Priority ctrl = SLAVE
#RunHrsMaxDiff = 9h
RunHoursBase = 0 h
Control group =
COMMON
Values: Statistics
Run hours = 10 h
Comms settings:
Contr. Addr = 4
Comms settings:
Nomin power =
200 kW
Pwr management:
#PriorAutoSwap =
EFFICIENCY
Priority ctrl = SLAVE
#RunHrsMaxDiff = 9h
RunHoursBase = 0 h
Control group =
COMMON
Values: Statistics
Run hours = 20 h
Comms settings:
Contr. Addr = 5
Comms settings:
Nomin power =
100 kW
Pwr management:
#PriorAutoSwap =
EFFICIENCY
Priority ctrl = SLAVE
RunHoursBase = 0 h
Control group =
COMMON
2
3
4
5
GCB
1
GCB
2
GCB
3
GCB
4
GCB
5
Inteli
Mains
Comms settings:
Contr. Addr = 6
Pwr management:
#PriorAutoSwap =
EFFICIENCY
Priority ctrl = MASTER
Control group =
COMMON
Setpoint group
Basic settings
Pwr management
Setpoint
Nomin power / RHE
Pwr management #Pwr mgmt mode Priority #PriorityAutoSwap #LoadResStrt X #LoadResStop X
Gen-set #1
300 kW
ENABLED
ABS (kW)
1
EFFICIENCY
20 kW
30 kW
Gen-set #2
200 kW / 0 h
ENABLED
ABS (kW)
2
EFFICIENCY
Gen-set #3
200 kW / 10 h
ENABLED
ABS (kW)
3
EFFICIENCY
Gen-set #4
200 kW / 20 h
ENABLED
ABS (kW)
4
EFFICIENCY
Gen-set #5
100 kW
ENABLED
ABS (kW)
5
EFFICIENCY
N
OTE
:
Gen-set #1 means that the CAN address of the controller is set to 1. The relevant setpoint is adjusted
by
Comms settings:
Contr. address
.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...