InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
233
11.2.9.6
Setpoint: #LoadResStrt 1
Group
Pwr Management
Range [units]
-32000 ..
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the load reserve for start in absolute mode. i.e.
= ABS (kW) or ABS (kVA) if the reserve set #1 is active.
Learn more about reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
If the absolute power management is selected, this setpoint (or the setpoints
reserve set is selected) determines also the number of gensets (that are part
of the power management) which will start (according to their priority and
nominal power).
N
OTE
:
There is a possiblity to assign this setpoint negative number. This can be
used in some situations to allow genset start after Sys Start/Stop gets active.
It is not destined for normal operation. Please refer to the Troubleshooting
guide for more information (chapter "MGCB is not closed although gensets
are running").
N
OTE
:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
11.2.9.7
Setpoint: #LoadResStop 1
Group
Pwr Management
Range [units]
Related FW
standard v3.1.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
= ABS (kW) or ABS (kVA) if the reserve set #1 is active.
Learn more about reserves in the chapter
Reserves, minimal running power
.
The currently active reserve set is selected by binary inputs
. If none of these inputs is active the set #1 is selected.
N
OTE
:
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...