Required Power from Gen-set group
Power Consumption of the Load
Power imported from Mains
0
0
0
Import
/Export
Controller decreases the required power from gen-
set group to maintain the constant level of Import
from Mains as the load consumption decreases
No power is taken from the gen-set group and
the load consumption still goes down, so the
Import from Mains cannot be maintained on the
constant level and it is starting to lower as well