InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
149
10
Controller operation states
These states are given by requested breaker positions and other parameters (e.g. healthy Mains).
Controller can operate in following states.
MainsOper MCB application: MCB feedback is active, all GCB feedbacks are not active, Mains parameters
are within limits
MGCB application: MCB feedback is active, MGCB feedback is not active, Mains parameters
are within limits
MainsFlt
MCB application: Mains parameters are not within limits
MGCB application: MGCB feedback is not active, Mains parameters are not within limits
ValidFlt
MCB application: Mains parameters are not within limits and
AMF settings
:
EmergStart del
elapsed
MGCB application: MGCB feedback is not active, Mains parameters are not within limits and
AMF settings
:
EmergStart del
elapsed
IslOper
MCB application: MCB feedback is not active, at least one GCB feedback is active, Mains
parameters are not within limits
MGCB application: MCB feedback is not active, MGCB feedback is active, Mains parameters
are not within limits
MainsRet
MCB application: MCB feedback is not active, at least one GCB feedback is active, Mains
parameters are within limits
MGCB application: MCB feedback is not active, MGCB feedback is active, Mains parameters
are within limits
BrksOff
MCB application: MCB and all GCB feedback are not active
MGCB application: MCB and MGCB feedbacks are not active
Synchro
MGCB application: MCB feedback is active, MGCB feedback is not active, synchronization is
allowed and started
RevSync
MCB application: MCB feedback is not active, at least one GCB feedback is active, reverse
synchronization is allowed and started
MGCB application: MCB feedback is not active, MGCB feedback is active, reverse
synchronization is allowed and started
ParalOper
MCB application: MCB feedback is active, at least one GCB feedback is active
MGCB application: MCB and MGCB feedbacks are active
EmergMan Controller is in this state if BI E
MERG
.
MANUAL
is activated. In this state controller does not react
on breaker changes and do not activate any of its binary outputs. For more information please
refer to E
MERG
.
MANUAL
description in the APPENDIX of this manual or see context help in
GenConfig.
Init
Initialization of controller. In this state, controller is not fully functional.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...