InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
116
A
PPLICATION
V
OLTAGE GAIN AND
V
OLTAGE INT SETPOINTS ARE ACTIVE DURING
:
MCB
reverse synchronization of the gen-set group back to the mains
MGCB
forward or reverse synchronization of the gen-set group to the
mains
See also setpoints:
Volt/PF ctrl:
Voltage gain
and
Volt/PF ctrl:
Voltage Int
When the Voltage gain is set to zero, this control loop is switched OFF.
C
OS
-
PHI
LOOP
This regulation loop is active if setpoint
ProcessControl:
SysPFCtrl PtM
is set to
VSHARING.
ProcessControl:
SysLdCtrl PtM
should be swithed to LDSHARING.
The IM power factor control mode is selected by the
setpoint
ProcessControl:
PF ctrl PtM
.
ProcessControl:
MLoad ctrl PtM
should be set to the same value
as
ProcessControl:
PF ctrl PtM
. Due to this Cos-phi regulation loop can be
active only in the Import/Export mode.
7.12.1 PI regulation adjustment
The regulation loops have two adjustable factors: P-factor and I-factor (except angle regulation loop,
which has P-factor only). The P-factor (gain) influences the stability and overshoot of the regulation
loop and the I-factor influences the steady-state error as well as the settling time. See the picture
below for typical responses of a PI regulation loop.
Figure:
Typical responses of a PI regulator
For manual tunning of a control loop use following method:
1. Set both the I-factor and P-factor to 0.
2. Increase the P-factor slightly until the system starts to oscillate.
3. Adjust the P-factor back to approx. one half of the value where the oscillations started.
4. Increase the I-factor slightly to achieve optimal resulting response.
N
OTE
:
It may be helpful to disable issuing the breaker close command when adjusting synchronization loops.
Adjust the setpoint
to 0 to disable it. Adjust the setpoint back to its original value after
the adjustment is finished.
C
AUTION
!
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...