reset again when they become inactive.
ENABLED
Pressing of the fault reset button (at any terminal or
external button) resets
all
alarms that are currently
present in the alarm list. Inactive alarms disappear from
the alarm list immediately, active alarms are changed to
"confirmed" state and disappear when the alarm condition
disappear or the alarm starts to be blocked.
N
OTE
:
ENABLED position corresponds to the method how the IG-classic and IS-
classic controllers handled the alarms.
11.2.5 Group: Analog protect
11.2.5.1
Setpoint: Batt >V
Group
Analog protect
Range [units]
8.0 .. 40.0 [V]
Related FW
standard v3.1.0
Description
This setpoint adjusts the warning level for battery overvoltage alarm.
11.2.5.2
Setpoint: Batt <V
Group
Analog protect
Range [units]
8.0 .. 40.0 [V]
Related FW
standard v3.1.0
Description
This setpoint adjusts the warning level for battery undervoltage alarm.
11.2.5.3
Setpoint: Batt volt del
Group
Analog protect
Range [units]
0 .. 600 [s]
Related FW
standard v3.1.0
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...