InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
390
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
C
AUTION
!
All controllers cooperating together in Power management must have
the
same minimal running power selected.
N
OTE
:
It is possible to use
virtual peripheries
for distribution of the binary signal from
one physical switch connected to one controller to all other controllers over
the CAN bus. See the principial diagram of such distribution in the description
of the input
13.2.1.106
Binary input: MinRun power 3
Related FW
standard v3.1.0
Description
This input is used to activate the function Minimal running power #3, which is
adjusted by setpoint
N
OTE
:
The default value of minimal running power, which takes place while none of
the inputs
MinRun power x
, is 0kW.
N
OTE
:
If more then one binary input for MinRunPower is activated, the one with the
highest number is used (i.e. its corresponding value).
C
AUTION
!
All controllers cooperating together in Power management must have
the
same minimal running power selected.
N
OTE
:
It is possible to use
virtual peripheries
for distribution of the binary signal from
one physical switch connected to one controller to all other controllers over
the CAN bus. See the principial diagram of such distribution in the description
of the input
13.2.1.107
Binary input: MCBIsolated
Related FW
standard v3.1.0
Description
This input can be used for secondary breaker feedback. When this logical
binary input gets activated the controller will consider the corresponding CB
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...