Available functions for soft buttons are listed in the following table.
ON
Pressing the button changes the state of log. Binary Output U
SER BUTTON
X to
closed. When the output is closed and the button is pressed state is not changed.
OFF
Pressing the button changes the state of log. Binary Output U
SER BUTTON
X to
opened. When the output is opened and the button is pressed state is not changed.
ON/OFF
Pressing the button changes the state of log. Binary Output U
SER BUTTON
X to
opened or closed depending on previous state (it is changed to the opposite state).
P
ULSE
ON
Pressing the button issues log. Binary Output U
SER BUTTON
X to close for the time
given by setpoint
Basic settings:
UserBtn pulse
(from 0.2s to 10s).
N
OTE
:
Repeated pressing of button during the closed period causes issuing other puls of
length of the given length to be generated from the moment of button pushing.
H
INT
It is possible to lock User Button with password (go to tab Commands in GenConfig). User Buttons 1-
5, 6-8 and 9-16 can be locked separately. It is also possible to use User Buttons in SCADA diagrams.
7.18 Remote Control Function
It is possible to remotely control several Binary Outputs in the controller. You can either use Remote
Switches tool in InteliMonitor (select Remote switches in menu for corresponding controller), import
Remote Switches tool to a SCADA diagram in Line Diagram Editor or use external device via Modbus
(register #46361 and command #26 (1A hex), for more information on Modbus please refer to the
InteliGen/InteliSys Communication guide).
Remote Switch will activate or deactivate depending on remote control so it can be used to manually
control devices, simulate malfunctions while commissioning etc.
Figure:
Remote Switches tool in InteliMonitor, Remote Switches tools in Line Diagram Editor and Mobus commands
Remote Switches may be easily used to trigger logical Binary Input function and all other related
functions as normal switch on Binary Input. Module VPIO (Virtual Peripheral Inputs- Outputs) can be
added to configuration and it will copy the state of Remote Switch on virtual output to its counterpart
virtual input. Refer to the figure below for example.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...