InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
195
information about MODBUS protocol.
MODBUS-MDM(HW)
Modbus RTU connection in slave mode via
modem with hardware data flow control. The
communication speed is adjustable by the
setpoint
. See the latest
communication guide for more information about
MODBUS protocol.
ECU-LINK
Connection to an electronic-controlled engine
which uses non-J1939 ECU. The proper ECU
type must be also configured with GenConfig.
N
OTE
:
The COM2 prot is not available in the basic IG-NT version.
N
OTE
:
The RS232 connector is no more available in hardware version 2.0 and
above. The COM2 port is redirected to the RS485(2) terminals all the time.
That means modem is not supported at COM2 in these hardware versions.
For modem use the COM1 port instead.
11.2.3.6
Setpoint: RS232(1)MBCSpd
Group
Comms settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related FW
standard v3.1.0
Description
The setpoint adjusts the communication speed on the COM1 connector when
it is switched to MODBUS or MODBUS-MDM(HW) mode. See also the
setpoint
11.2.3.7
Setpoint: RS232(2)MBCSpd
Group
Comms settings
Range [units]
9600, 19200, 38400, 57600 [bps]
Related FW
standard v3.1.0
Description
The setpoint adjusts the communication speed on the COM2 connector when
it is switched to MODBUS or MODBUS-MDM(HW) mode. See also the
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...