InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
135
8
Protections and Alarm management
ComAp mains controllers provide following range of mains protections.
For each protection adjustable limit and time delay are available.
ANSI
CODE
P
ROTECTION
IM-NT,
IM-NT-BB
25
Synchronism Check
27
Undervoltage
32P
Load Shedding
37
Undercurrent
@
46
Current Unbalance
47
Voltage Unbalance and Phase-sequence
49T
Temperature Monitoring (using configurable Analog
input)
@
51
AC Inverse Time Overcurrent
55
Power Factor
@
59
Overvoltage
78
Vector Shift
79
AC Reclosing
81H
Overfrequency
81L
Underfrequency
81R
ROCOF
N
OTE
:
- included
@
- example of protections that can be created using universal protections (it is possible to utilize
controller functions to prepare even more protections)
8.1.1
Protection groups
P
ROTECTION
G
ROUP
C
OFIGURABILITY
S
ETPOINT
G
ROUP
Analog protections
Configurable
Analog protect
Mains protections
Configurable
Mains protect
Fixed protections
Fixed
Mains protect
Bus protect
8.1.2
Protection types
L
EVEL
P
ROTECTION
T
YPE
A
BBREVI
ATION
C
ONTROLLER
A
CTION
R
ECORD
F
AULT
R
ESET
N
EEDED
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...