11.2.6.18
Setpoint: ROCOF df/dt
Group
Mains protect
Range [units]
0.1 .. 10.0 [Hz/s]
Related FW
standard v3.1.0
Description
This setpoint adjusts the trip level for ROCOF protection (Rate Of Change Of
Frequency). The "filtration level" for the ROCOF protection is adjusted by
setpoint
N
OTE
:
If measured value of df/dt exceeds ROCOF df/dt, ROCOF protection is
activated. The message ROCOF is writen in history of controller and
corresponding logical binary output is activated
. Value of df/dt is
evaluated from mains voltage.
N
OTE
:
To activate or deactivate ROCOF protection, please use
Choose proper breaker which will be opened if ROCOF protection activates
by adjusting setpoint
11.2.6.19
Setpoint: Mains V unbal
Group
Mains protect
Range [units]
0 .. 200 [%]
Related FW
standard v3.1.0
Description
This setpoint defines the threshold level for Mains voltage unbalance
protection. The voltage unbalance is calculated as a maximum difference
between phase voltages. This protection is evaluated with delay given by
11.2.6.20
Setpoint: Mains Vunb del
Group
Mains protect
Range [units]
0.0 .. 600.0 [s]
Related FW
standard v3.1.0
Description
This setpoint adjusts delay for mains voltage unbalance alarm (see
).
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...