InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
69
7.6.2.2
Load reserve
The power management is based on the load reserve concept. The load reserve is defined as
a difference of the running nominal power of the group within power management and the total load of
the system. There are two ways how to determine the load reserve. The absolute power management
allows the system to keep the load reserve higher or equal to value in kW or kVA given by a relevant
setpoint. The relative power management assures that load reserve is kept higher or equal to relative
portion in % of the nominal power of group (i.e. running gen-sets active in power management) given
by a relevant set-point. Depending of the situation, load reserves are calculated differently in two
cases:
Case #1:
island operation
or parallel to mains operation,
ProcessControl:
#SysLdCtrl PtM
= LDSHARING
Reserve
Actual Reserve
Start condition
Stop condition
Absolute
kW / kVA
ARstrt = ΣPg
Nom
– ΣPg
Act
ARstp = ΣPg*
Nom
– ΣPg
Act
ARstrt <
#LoadResStrt
ARstp >
#LoadResStop
Relative
%
RRstrt = [(ΣPg
Nom
– ΣPg
Act
) /
ΣPg
Nom
].100%
RRstp = [(ΣPg*
Nom
– ΣPg
Act
) /
ΣPg*
Nom
].100%
RRstrt <
#%LdResStrt
RRstp >
#%LdResStop
Case #2:
parallel to mains operation,
ProcessControl:
#SysLdCtrl PtM
= BASELOAD
Reserve
Actual Reserve
Start condition
Stop condition
Absolute
kW / kVA
ARstrt = ΣPg
Nom
– BaseLd
ARstp = ΣPg*
Nom
– BaseLd
ARstrt <
#LoadResStrt
ARstp >
#LoadResStop
Relative
%
RRstrt = [(ΣPg
Nom
– BaseLd) / ΣPg
Nom
].100%
RRstp = [(ΣPg*
Nom
– BaseLd) / ΣPg*
Nom
].100%
RRstrt <
#%LdResStrt
RRstp >
#%LdResStop
Where
ARstrt
Actual Absolute reserve in kW or kVA - for engine start calculation.
ARstp
Actual Absolute reserves in kW or kVA - for engine stop calculation.
RRstrt
Actual Relative reserve in % - for engine start calculation.
RRstp
Actual Relative reserves in % - for engine stop calculation.
ΣPg
Nom
Sum of Nominal power of all gen-sets on the bus.
ΣPg*
Nom
Sum of Nominal power of all gen-sets on the bus apart of the one, which is going to be
stopped.
ΣPg
Act
BaseLd
Sum of Actual power of all gen-sets on the bus = system load.
Baseload is given by the setpoint
ProcessControl:
#SysBaseLoad
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...