11.2.11 Group: Volt/PF ctrl
11.2.11.1
Setpoint: Voltage gain
Group
Volt/PF Ctrl
Range [units]
0.0 .. 200.0 [%]
Related FW
standard v3.1.0
Description
This setpoint adjusts the gain factor (P-factor) of the voltage control PI loop.
The integration factor (I-factor) for the voltage control loop is adjusted by the
setpoint
N
OTE
:
If this setpoint is set to 0 the regulation loop is disabled.
A
PPLICATION
V
OLTAGE GAIN AND
V
OLTAGE INT SETPOINTS ARE ACTIVE DURING
:
MCB
reverse synchronization of the gen-set group back to the
mains
MGCB
forward or reverse synchronization of the gen-set group to the
mains
BTB
synchronization between “left” and “right” buses
N
OTE
:
When this setpoint is set to zero, the corresponding control loop is switched
OFF.
N
OTE
:
See the chapter
Regulation loops overview
for general information about
regulation loops and their adjustment.
11.2.11.2
Setpoint: Voltage Int
Group
Volt/PF Ctrl
Range [units]
0 .. 100 [%]
Related FW
standard v3.1.0
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...