InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
177
N
OTE
:
Example: if you have transformers with ratio 6000/100V adjust the setpoint to
the value of
60.00
.
N
OTE
:
The range of the bus voltage inputs must be adjusted properly. See the
setpoint
11.2.2.4
Setpoint: BusInpRangeSel
Group
Basic settings
Range [units]
277V, 120V [-]
Related FW
standard v3.1.0
Description
This setpoint selects the range of the bus voltage terminals. The 120V range
is available only in IM-NTC hardware. The IM-NT has the range adjusted
fixedly to 277V regardless of this setpoint.
N
OTE
:
The 277V range is suitable for both European (230V) and American (277V)
measurement. The range 120V is intended for high-voltage applications
where voltage transformers with 100V secondary range are used or for
alternative American (120V) measurement.
11.2.2.5
Setpoint: MainsNomV
Group
Basic Settings
Range [units]
10 .. 30000 [V]
Related FW
standard v3.1.0
Force value
possible
YES
Description
This setpoint is used to adjust the nominal mains voltage (phase to neutral).
If you do not know the phase-neutral nominal voltage, you can adjust the
phase-phase nominal voltage
. The controller will then
recalculate the phase-neutral nominal voltage automatically.
N
OTE
:
The actual setpoint units and range depend on setting of the Power format in
GenConfig.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...