InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf,
©ComAp – April 2015
123
LBO:RemoteControl1
LBI:Emerg. manual
Remote Switch
command
Vitual Output
Virtual Input
1
2
3
4
5
6
7
8
VPIO module
Figure:
Using of Remote Switches to trigger logical binary inputs
7.19 Virtual Peripheral Inputs-Outputs (VPIO) module
For InteliMains there are several modules available. One of them is Virtual Peripheral Inputs-Outputs
module which is particularly usefull for connection of logical Binary Output functions to logical Binary
Input functions. This way internal controller function may easily trigger other internal controller
functions without unnecessary wiring or usage of PLC functions.
Module is functioning the same way as normal module with 8 outputs and 8 inputs, but the difference
is, that each input copies its counterpart output. It is possible to select any logical Binary Output
function for one of the outputs of VPIO module. Inputs on VPIO module work the same way as
standard input of the controller (i.e. it can be assigned function and protection).
For example of this function please refer to the chapter Remote Control function.
7.20 Shared Inputs and Outputs
InteliMains uses the same type of Shared Inputs and Outputs (SHBOUT, SHBIN, SHAIN and
SHAOUT modules) as InteliGen and InteliSys. Thanks to this, it is possible to share Binary and Analog
values between all the controllers via CAN bus, thus saving physical Inputs and Outputs and excess
wiring.
Содержание InteliMains NT IM-NT
Страница 150: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 150 APPENDIX...
Страница 435: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 435 16 User Notes...
Страница 436: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 436...
Страница 437: ...InteliMains NT SW version 3 2 0 InteliMains NT MCB MGCB 3 2 0 Reference Guide pdf ComAp April 2015 437...