Instructional Leaflet IL0131093EN

Supersedes May 2015
Effective January 2019

Power Defense – ICCB 

Power

 

Defense™

Instructions for secondary terminal 

blocks

Instructions Apply to:

WARNING

(1)  ONLY QUALIFIED ELECTRICAL PERSONNEL SHOULD BE 

PERMITTED TO WORK ON THE EQUIPMENT. 

(2)  ALWAYS DE-ENERGIZE PRIMARY AND SECONDARY CIRCUITS IF 

A CIRCUIT BREAKER CANNOT BE REMOVED TO A SAFE WORK 
LOCATION.

(3)  DRAWOUT CIRCUIT BREAKERS SHOULD BE LEVERED (RACKED) 

OUT TO THE DISCONNECT POSITION.

(4)  ALL CIRCUIT BREAKERS SHOULD BE SWITCHED TO THE OFF 

POSITION AND MECHANISM SPRINGS DISCHARGED.

FAILURE TO FOLLOW THESE STEPS FOR ALL PROCEDURES 

DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN 
DEATH, BODILY INJURY, OR PROPERTY DAMAGE.

WARNING

THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT 
LABELS HAVE TO BE FOLLOWED. OBSERVE THE FIVE SAFETY RULES:
– DISCONNECTING
– ENSURE THAT DEVICES CANNOT BE ACCIDENTALLY RESTARTED
–  VERIFY ISOLATION FROM THE SUPPLY
–  EARTHING AND SHORT-CIRCUITING
–  COVERING OR PROVIDING BARRIERS TO ADJACENT LIVE PARTS
DISCONNECT THE EQUIPMENT FROM THE SUPPLY.  USE ONLY 
AUTHORIZED SPARE PARTS IN THE REPAIR OF THE EQUIPMENT.  
THE SPECIFIED MAINTENANCE INTERVALS AS WELL AS THE 
INSTRUCTIONS FOR REPAIR AND EXCHANGE MUST BE STRICTLY 
ADHERED TO PREVENT INJURY TO PERSONNEL AND DAMAGE TO 
THE SWITCHBOARD.

UL489 

: PD-RF

IEC 

: PD-RF, IZMX40

UL489 

 

: PD-NF

IEC 

 

: PD-NF, IZMX16

Содержание Power Defense PD-NF

Страница 1: ...FOLLOW THESE STEPS FOR ALL PROCEDURES DESCRIBED IN THIS INSTRUCTION LEAFLET COULD RESULT IN DEATH BODILY INJURY OR PROPERTY DAMAGE WARNING THE INSTRUCTIONS CONTAINED IN THIS IL AND ON PRODUCT LABELS...

Страница 2: ...rs secondary terminal blocks Figure 1 are mounted onto an insulated support frame on the top front portion of the drawout cassette Figure 1 Drawout Terminal Block For fixed mounted circuit breakers se...

Страница 3: ...Step 3 Become familiar with the fixed terminal block mount ing plate where secondary connections are made Note N Secondary connection points have numerical and descriptive laser etched identifications...

Страница 4: ...IMPORTANT KEEP IN MIND THAT THE SECONDARY TERMINAL BLOCKS ASSOCI ATED WITH DRAWOUT CIRCUIT BREAKERS ARE MOUNTED ON THE BREAKER S DRAWOUT CASSETTE FIGURE 11 ACCESSORY SECOND ARY PLUGS PLUG INTO A SECO...

Страница 5: ...aker s secondary plug housing to ensure accurate terminal block placement In addition a terminal block alignment bracket is assembled to provide proper alignment and separation of each individual term...

Страница 6: ...etween any mounted terminal blocks and put it aside for re installment after new terminal blocks are connected to the mounting bracket Figure 16 Step 3 Grasp Here Step 4 Connect the bottom part of the...

Страница 7: ...Step 8 Step 9 Once the terminal block alignment bracket is in place inspect it from the bottom to ensure that the teeth on the bracket separate each individual terminal block Only one installed termin...

Страница 8: ...tual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equipm...