GEH-62808
Power Break® II Circuit Breaker
Accessories
Mechanical Counter
Introduction
The Mechanical Counter, shown in Figure
1,
can be
installed in
800-4000
ampere frame Power Break® II
circuit breakers. Its function is to count the number of
times the breaker is closed. The catalog number when
ordered with a circuit breaker for factory installation is
SPCOUNTER. The catalog number of the field
installable Mechanical Counter kit is SPCOUNTERR.
Figure
1.
Mechanical Counter.
Operation
The count displayed by the Mechanical Counter is
incremented each time the circuit breaker is closed.
Installation
WARNING:
Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources, and
discharge the closing springs.
AVERTISSEMENT:
Avant d'installer tout accessoire,
mettre le disjoncteur en position OFF, le deconnecter
de toute tension d'alimentation, et decharger les
ressorts d'armement
Install the Mechanical Counter with the following
procedure.
1.
Turn off the breaker, discharge the springs, and
turn off control power to the accessories and
motor operator (if present). If it is a draw-out
breaker, rack it out.
2.
Loosen the four
#8-32
screws on the trim-plate
assembly and remove the trim plate.
3.
Loosen the four screws at the corners of the
breaker cover. Remove the cover from the breaker
face.
4.
On the breaker cover, use a screwdriver to punch
out the knockout above the
CHARGE-DISCHARGE
flag opening.
5.
Hold the ON-OFF flag towards the ON position,
then carefully insert the flag lockout plate to retain
the flag in this position. The flag lockout plate
should be installed close to the side frame on
which the
ON-OFF
flag pivots and over the larger
diameter portion of the mechanism cross pin.
The installed flag lockout plate is shown in Figure
2.
LOCKOUT
PLATE
Figure
2.
Flag lockout plate installed in breaker.
6.
Locate the two mounting holes through the side
frame, behind the
CHARGE-DISCHARGE
flag.
Place the spring-loaded Mechanical Counter arm
above the tab on the
ON-OFF
flag, while
simultaneously inserting the two pins on the
Mechanical Counter through the holes in the side
frame.
7.
Slide the straight legs of the provided clip over the
pin on the Mechanical Counter furthest from the
ON-OFF
flag. Rotate the clip counter-clockwise
until the circular part of the clip snaps over the
second pin on the Mechanical Counter.
8.
Carefully remove the flag lockout plate, allowing
the
ON-OFF
flag to return to the
OFF
position. The
installed Mechanical Counter is shown in Figure
3.
www
. ElectricalPartManuals