PLC
232
9836 3521 01
Use the below output signals to control the behavior of the bolts:
Variable
Type
Use
BOLTCONTROL
ARRAY[1..50]
OF BYTE
This output controls which bolts to run when the station is started.
Takes one of the following values:
0: Connect normally. The bolt will run the tightening program
specified in the mode table when station is started.
1: Disconnected with OK status
2: Disconnected with NOK status
3: Do not run during next cycle
100 + Pgm. No: The bolt will run the tightening program with
program number Pgm. No when station is started and mode
table value is “Program from PLC” for the bolt. PgmNo is a
number between 1 and 150.
The difference between "Disconnected" and "Do not Run" is that
in the first case the bolt will be reported with the given status and
in the latter nothing is reported for the bolt. In neither case will the
bolt start when the station is started.
The outputs BOLTCONTROL and DATAHOLD are useful when running a stitching application, i.e. when a
single spindle is used to tighten more than one bolt. To generate one cycle data result, including only one
station header, even though several starts are done follow the below scheme:
1. Set DATAHOLD = True
2. Set BOLTCONTROL = 0 or BOLTCONTROL = 100 + Pgm. No for all bolts to run in this cycle and
BOLTCONTROL = 3 for all bolts that should not.
3. Generate a START. This will start only the selected bolts.
4. Wait for the cycle to end (monitor for example STATIONSTATUS)
5. If not all bolts are tightened yet go to step 2
6. Set DATAHOLD = False to release the cycle data, complete with one record for the station and
one for each bolt tightened
Содержание PowerMACS 4000
Страница 1: ...User guide PowerMACS 4000 Atlas Copco Tools and Assembly Systems 9836 3521 01 2010 11 Edition 10 3 0...
Страница 2: ......
Страница 46: ...System Architecture 46 9836 3521 01...
Страница 127: ...Set Up and Maintenance 9836 3521 01 127 See chapter Station Set Up for a description of the parameters...
Страница 267: ...Tightening 9836 3521 01 267...
Страница 400: ...Tightening 400 9836 3521 01...
Страница 422: ...Peripheral Devices 422 9836 3521 01 When connected to a system the form will show show the signal values in realtime...
Страница 486: ...Peripheral Devices 486 9836 3521 01...
Страница 622: ...Peripheral Devices 622 9836 3521 01...
Страница 664: ...References 664 9836 3521 01...
Страница 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...