Peripheral Devices
9836 3521 01
597
Use
Name
to specify the name of the device.
Enter the
Node addr.
(can be [0..63]) and
Baud Rate
(can be 125, 250 or 500 kBit/s).
Specify in
Bytes In
the number of input bytes, this could be either 4 or 8 depending on if the PVI number
should be read from the fieldbus or not.
Depending on the number of spindles in the system set
Bytes Out
to 4 for a station with 1 to 5 spindles,
and 8 for a station with 6 to16 spindles.
Specify in
Turn of light timeout
how many seconds the external tool lights should present the result of
the rundown (max 60 seconds). Specify 0 if the tool lights should remain on to the next rundown cycle.
The checkbox
Flash tool light on rising EPR signal
controls whether or not the green tool lights should
start to flash when a positive edge is detected on the Error Proofing Ready input signal. If checked the
tools will flash.
Use the checkboxes in the
Rundown control signals
frame to select which interface that should be
active. It is possible to have both interfaces active at the same time. If both are active then the
corresponding input signals will be OR:ed together.
Note 1
: To ensure Operator Safety it is possible to disable all of the input bits from the DeviceNet interface
as well as the discrete I/O interface. Uncheck the checkbox in the
Rundown control signals
frame that corresponds to the interface you want to disable.
It is also possible to disable all DeviceNet inputs except for the PVI number using the PLC output
GM_IN.DISABLEDNETINP (normally mapped to the digital input DI_GM_DisableDNetInp). This
signal is read by the GM Device regardless of the value of the
Through discrete I/O
. See also
chapter: GM DeviceNet variables.
Note 2
: When using this device type you must ensure that the ANYBUS_in and ANYBUS_out drivers of
the PowerMACS PLC are disabled. This is done using the I/O Configuration dialogue opened by
double-clicking on the
IO_Configuration
worksheet of the Station that has the fieldbus interface
mounted. See chapter: Access to PLC data for details.
Also, since the interface layout is fixed it is not possible to create a reporter for a device of this
type.
For more information on the DeviceNet fieldbus, for example the meaning of the status indication LED's,
see chapter: Fieldbus Interface.
Содержание PowerMACS 4000
Страница 1: ...User guide PowerMACS 4000 Atlas Copco Tools and Assembly Systems 9836 3521 01 2010 11 Edition 10 3 0...
Страница 2: ......
Страница 46: ...System Architecture 46 9836 3521 01...
Страница 127: ...Set Up and Maintenance 9836 3521 01 127 See chapter Station Set Up for a description of the parameters...
Страница 267: ...Tightening 9836 3521 01 267...
Страница 400: ...Tightening 400 9836 3521 01...
Страница 422: ...Peripheral Devices 422 9836 3521 01 When connected to a system the form will show show the signal values in realtime...
Страница 486: ...Peripheral Devices 486 9836 3521 01...
Страница 622: ...Peripheral Devices 622 9836 3521 01...
Страница 664: ...References 664 9836 3521 01...
Страница 668: ...9836 3521 01 2010 11 Edition 10 3 0 www atlascopco com...