Communications configuring
3-220
System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
Interconnection possibilities using BICO technology and their
significance:
Pseudo- Con-
nection-
Inter-
connected
Processed at the operator control device
comment Type
with
Read
Write
@TP_L/H
I
Standard
Display value
Not possible
@TP_L/H
I
Flag
Display value
Change value
@TP_L/H
I
$ signal
Display value
Not possible
@TP_L/H I
Virtual inter-
connection
Display value
Not possible
@TP_L/H
I
—
Display value
Change value
@TP_L/H I
@TC_
Display the number of the
@TC_
Interconnect to a new number
of @TC_, if present
@TP_c/d
I
Any
Display value
Not possible
@TP_c/d
I
@TC_
Display value
Not possible
@TP_L/H
O
Any
Display value
Not possible
@TP_c/d
O
Any
Display value
Not possible
@TC_
I
—
Error message when compiling in the CFC
@TC_
O
—
Source for interconnection using BICO technology
Legend
@TP_L/H:
Parameter @TP_Lnnn or @TP_Hnnn
@TP_c/d:
Parameter @TP_cnnn or @TP_dnnn
@TC_:
Technological connector @TC_nnnn
Standard:
The output is not a flag, not a $ signal and is not a virtual
interconnection.
Any:
Interconnected or not interconnected.
— :
No interconnection.
The number of newly generated interconnections between different tasks
using BICO technology is limited. The largest of the following values
applies for your application:
•
Value 20
•
20 % of the already configured number of interconnections between
tasks
•
0.25
×
number of the @TC_... technological connectors configured in
task n.
Examples
Interconnections
extending over
different tasks