Communications
configuring
System- and communication configuring D7-SYS - SIMADYN D
3-111
Edition 12.2003
Communications reference
:
Type: Cyclic
server
Association type
:
MSZY
Local LSAP
:
Remote address
:
Remote
LSAP
:
Max. PDU length
:
241
Supported utility
:
Read :
.ind
Write
:
.ind
Name :
Table 3-49
Mask, "Cyclic server"
Rules:
•
The communications reference is as required within the framework of
the general rules.
•
Local LSAP must coincide with the "Remote LSAP" of the remote
client.
•
The remote address and remote LSAP can be entered, defined, but
then only the appropriately selected client can establish a connection
(access protection!); or both values can be set to 255, and then the
association is open for all.
Features:
Cyclic data transfer with slaves
•
SIMADYN D is exclusively client.
•
An association must be configured for each object which SIMADYN D
accesses in the remote server.
•
SIMADYN D establishes the connection and initiates data transfer.
•
The object, which SIMADYN D accesses in the remote server is
defined by appropriate CFC configuring (address stage 2 at the
address input).
Application:
•
Process data, with SIMADYN D as client.
Cyclic client